General InformationSwitched Rack Power Distribution Units (PDUs) provide advanced load monitoring combined with remote on/off switching control of individual outlets for power cycling, delayed power sequencing, and outlet use management.Technical InformationPDU Type: SwitchedInput Receptacles: NEMA L5-30POutput Receptacles: 16 x NEMA 5-20RPower DescriptionInput Voltage: 120 V ACOutput Voltage: 120 VInput Current: 30 APhysical CharacteristicsMounting Orientation: HorizontalPlacement: RackRack Height: 2UHeight: 3.5"Width: 17.5"Depth: 4.5"Weight (Approximate): 9.92 lbMiscellaneousPackage Contents: Rack PDU, Switched, 2U, 30A, 120V, (16)5-20 Cord Retention Bracket(s) Horizontal Mounting Brackets Installation Guide User Manual Environmentally Friendly: YesEnvironmental Certification: RoHSEnvironmental Certification: REACHWarrantyLimited Warranty: 2 Year
| Output | |
|---|---|
| Nominal Output Voltage | 120V |
| Maximum Total Current Draw | 30 |
| Output Connections | (16) NEMA 5-20R (Battery Backup) |
| Input | |
| Nominal Input Voltage | 100V , 120V |
| Input frequency | 50/60 Hz |
| Input Connections | NEMA L5-30P |
| Cord Length | 3.05meters |
| Acceptable Input Voltage | 100-120VAC |
| Number of Power Cords | 1 |
| Load Capacity | 2880VA |
| Maximum Input Current | 30A |
| Regulatory Derated Input Current (North America) | 24A |
| Rack Height | 2U |
| Color | Black |
| Environmental | |
| Operating Environment | 0 to 45oC |
| Operating Relative Humidity | 0 - 95 % |
| Operating Elevation | 0-3000meters |
| Storage Temperature | -25 - 65oC |
| Storage Relative Humidity | 0 - 95 % |
| Storage Elevation | 0-15000meters |
| Conformance | |
| Approvals | cUL Listed, CSA, FCC Part 15 Class A, ICES-003, Industry Canada, UL 60950, UL Listed |
| Sustainable Offer Status | |
| RoHS | Compliant |
| REACH | REACH: Contains No SVHCs |
| Battery Directive | Compliant |
| Battery Notes | ts_Battery_Notes |
| Item Dimension (L inchxW inchxH inch) | 15 x 15 x 6 |
| Weight | 14.40 lb |
| Warranty Information | 2 Years |