| OUTPUT | |
|---|---|
| Output Volt Amp Capacity (VA) | 6000 |
| Output kVA capacity (kVA) | 6.0 |
| Output Watt Capacity (watts) | 5400 |
| Output kW capacity | 5.4 |
| Output power factor | 0.9 |
| Crest Factor | 3:1 |
| Nominal Output Voltage(s) Supported | 200V 208V 220V 230V 240V |
| Frequency compatibility | 50/60 Hz (auto-selectable) |
| Frequency compatibility details | Output frequency matches input nominal on startup Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating) |
| Output voltage regulation (line mode) | +/- 2% |
| Output voltage regulation (Economy line mode) | +/- 10% |
| Output voltage regulation (Battery mode) | +/- 2% |
| Built-in UPS output receptacles | Hardwire |
| Output receptacle details | Hardwire input and output connections are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement |
| Output AC waveform (AC mode) | Pure Sine wave |
| Output AC waveform (battery mode) | Pure Sine wave |
| INPUT | |
| Rated input current (at maximum load) | 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V) |
| Nominal Input Voltage(s) Supported | 200V AC 208V AC 220V AC 230V AC 240V AC |
| UPS input connection type | Hardwire |
| BATTERY | |
| Full load runtime (minutes) | 2 minutes (5400 watts) |
| Half load runtime (minutes) | 8.5 minutes (2700 watts) |
| Expandable battery runtime | Runtime is expandable with external battery packs |
| External battery pack compatibility | BP192V12-3U |
| DC system voltage (VDC) | 192 |
| Battery recharge rate (included batteries) | 6 hours from 10% to 90% (internal batteries) |
| Replacement battery cartridge (internal UPS battery replacement) | RBC5-192 |
| Battery Access | Front panel battery access door |
| Battery replacement description | Hot-swappable, user replaceable internal batteries |
| LEDS ALARMS SWITCHES | |
| LED Indicators | 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status LCD screen offers additional information and control options |
| Alarms | Unique audible alarms for all major UPS, environmental and power conditions (see manual) |
| Alarm cancel operation | Alarm cancel switch |
| SURGE / NOISE SUPPRESSION | |
| UPS AC suppression response time | Instantaneous |
| EMI / RFI AC noise suppression | Yes |
| PHYSICAL | |
| Installation form factors supported with included accessories | 4 post 19 inch rackmount (mounting kit included) |
| Installation form factors supported with optional accessories | 2 post rackmount (2POSTRMKITHD) Tower (2-9USTAND) |
| Primary form factor | Rackmount |
| Installed whole system total rack space height (rack spaces) | 4U |
| UPS housing material | Steel |
| Cooling method | Fans |
| COMMUNICATIONS | |
| Communications interface | USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP/Web interface |
| Network monitoring port description | Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports |
| PowerAlert software | Included |
| Communications cable | USB, DB9 serial and EPO cables included |
| WatchDog compatibility | Yes |
| LINE / BATTERY TRANSFER | |
| Transfer time | No transfer time (0 ms.) in online, double-conversion mode |
| Transfer time (economy mode) | 8 ms. typical power failure response in optional economy mode |
| Low voltage transfer to battery power (setpoint) | 156V (full load) / 100V (50% load or less, derates linearly) |
| High voltage transfer to battery power (setpoint) | 280V (full load) / 300V (90% load or less) |
| SPECIAL FEATURES | |
| Cold Start (startup in battery mode during a power failure) | Cold-start operation supported |
| High availability UPS features | Automatic inverter bypass Manual bypass switch Detachable hot-swap PDU Hot swappable UPS power module Hot swappable batteries |
| Green high efficiency features | High efficiency economy mode operation Support for daily startup and shutoff Schedulable daily hours of economy mode operation |
| CERTIFICATIONS | |
| UPS Certifications | Tested to UL1778 (USA) Tested to CSA (Canada) Meets FCC Part 15 Category A (EMI) ROHS (Restriction of Hazardous Substances) |
| UPS Certification details | IEC 61000-4-5 1995 B Surge Immunity |
| Weight | 156.50 lb |
| Item Dimension (L"xW"xH") | 29.1 x 23.6 x 12.7 |
| Warranty Information | 250,000 connected equipment insurance |
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads