Output Capacity Details: DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
Power Factor: 0.9
Crest Factor: 3:1
Nominal Voltage Details: Nominal output voltage is user configured on first power-on
Frequency Compatibility: 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details: Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation
Output Voltage Regulation (Line Mode): +/- 2%
Output Voltage Regulation (Economy Line Mode): +/- 10%
Output Voltage Regulation (Battery Mode): +/- 2%
Load Management Receptacles: Two switchable outlet load banks (2 NEMA 6-15/20R outlets per bank)
Voltage Regulation Description: Online, double-conversion power conditioning
Overvoltage Correction: 2% output voltage regulation during overvoltages to 288
Undervoltage Correction: 2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
Front Panel LCD Display: Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options
Switches: 5 front panel switches: On/Off, Up, Down and Escape
Alarm Cancel Operation: Power-fail alarm can be silenced by following on-screen prompts
Audible Alarm: Audible alarm indicates power failure, low battery, overload and fault
LED Indicators: 4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
UPS Dataline Suppression Details: Single line dialup / network dataline protection included
EMI / RFI AC Noise Suppression: Yes
AC Suppression Joule Rating: 570
AC Suppression Response Time: Instantaneous
Primary Form Factor: Rackmount
Rack Height: 2U
Cooling Method: Fan
Included Mounting Accessory Description: 4 post installation accessories included
Installation Form Factors Supported with Included Accessories: 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories: 2 post rackmount ( 2POSTRMKITWM ); Tower ( 2-9USTAND )
Minimum Required Rack Depth (inches): 28
Minimum Required Rack Depth with External Battery Pack (cm): 77
Minimum Required Rack Depth with External Battery Pack (in.): 30.25
Minimum Required Rack Depth without External Battery Pack (cm): 74
Minimum Required Rack Depth without External Battery Pack (in.): 29.25
Primary UPS Depth (mm): 616
Primary UPS Height (mm): 88
Primary UPS Width (mm): 438
Shipping Dimensions (hwd / in.): 9.45 x 23.62 x 29.92
Shipping Weight (lbs.): 86.00
UPS Housing Material: Metal
UPS Power Module Dimensions (hwd, in.): 3.46 x 17.24 x 24.25
UPS Power Module Weight (kg): 32.12
UPS Power Module Weight (lbs.): 70.81
Unit Weight (lbs.): 70.8100
Operating Temperature Range: 32? to 104?F (0? to 40?C)
Storage Temperature Range: 5? to 122?F (-15? to 50?C)
Relative Humidity: 5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load): 933
AC Economy Mode BTU / Hr. (Full Load): 588
Battery Mode BTU / Hr. (Full Load): 1399
AC Mode Efficiency Rating (100% Load): >90%
AC Economy Mode Efficiency Rating (100% Load): >95%
Audible Noise: <50dB at front side 1M
Operating Elevation (m): Up to 3000m
Network Management Cards: SNMPWEBCARD; WEBCARDLX
Network Monitoring Port Description: Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 plus assignable contact closure pin functions for On-battery, On bypass, Output-on and Low-battery conditions and remote Shutdown, Output-off, Reboot and Power-toggle operations
PowerAlert Software: For local monitoring via the UPS's built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
Communications Cable: USB and DB9 cabling included
WatchDog Compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
Communications Interface: Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
Transfer Time: No transfer time (0 ms.) in online, double-conversion mode; 4 ms. transfer time during economy mode operation
Low Voltage Transfer to Battery Power (Setpoint): 160V (100% load), 140V (66% load), 120V (33% load)
High Voltage Transfer to Battery Power (Setpoint): 288V
Cold Start (Startup in Battery Mode During a Power Failure): Cold-start operation supported
High Availability UPS Features: Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic inverter bypass; Hot swappable batteries; Remote management; Surge/noise protection; Zero transfer time
Green Energy-Saving Features: High efficiency economy mode operation; Individually controllable load banks
Grounding Details: Back panel grounding lug included
UPS Applications: Mission Critical Applications
Product Certifications: CSA (Canada); NOM (Mexico); UL 1778
Product Compliance: RoHS; CE (Europe); ENERGY STAR Qualified; FCC Part 15 Class A (USA)
Product Warranty Period (Worldwide): 2-year limited warranty