OUTPUT Output Volt Amp Capacity (VA):1000 Output kVA Capacity (kVA):1 Output Watt Capacity (Watts):800 Power Factor:0.8 Nominal Output Voltage(s) Supported:120V Frequency Compatibility:60 Hz Output Voltage Regulation (Line Mode):-21%, +8% Output Voltage Regulation (Battery Mode):+/- 5% UPS Output Receptacles:6 5-15R outlet(s) Load Management Receptacles:Two switchable two-outlet 5-15R load banks Output AC Waveform (AC Mode):Sine wave Output AC Waveform (Battery Mode):Pure Sine wave INPUT Rated input current (Maximum Load):9.2A Nominal Input Voltage(s) Supported:120V AC UPS Input Connection Type:5-15P Input Circuit Breakers:10A UPS Input Cord Length (ft.):10 UPS Input Cord Length (m):3 Recommended Electrical Service:15A 120V Input Phase:Single-Phase BATTERY Full Load Runtime (min.):5.3 min. (800w) Half Load Runtime (min.):15 min. (400w) DC System Voltage (VDC):24 Battery Recharge Rate (Included Batteries):Less than 4 hours from 10% to 90% Internal UPS Replacement Battery Cartridge:See Tripp Lite UPS Battery Selector Battery Access:Front panel battery access door Battery Replacement Description:Hot-swappable, user replaceable batteries VOLTAGE REGULATION Voltage Regulation Description:Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147 Overvoltage Correction:Input voltages between 128 and 147 are reduced by 12% Undervoltage Correction:Input voltages between 83 and 107 are boosted by 14% LEDS ALARMS and SWITCHES Front Panel LCD Display:Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) Audible Alarm:Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions Alarm Cancel Operation:Power-fail alarm can be temporarily silenced using alarm-cancel switch silent mode alarm configuration option available Switches:3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions SURGE / NOISE SUPPRESSION UPS AC Suppression Joule Rating:570 UPS AC Suppression Response Time:Instantaneous EMI / RFI AC Noise Suppression:Yes Cooling Method:Fan UPS Housing Material:Steel COMMUNICATIONS Communications Interface:USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP/Web interface Network Monitoring Port Description:Supports detailed monitoring of UPS and site power conditions PowerAlert Software:Included Communications Cable:USB and DB9 cabling included WatchDog Compatibility:Supports Watchdog application, OS and hard-reboot restart options for remote applications Network UPS Tools Compatibility:NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.htmlmanufacturerTripp Lite LINE / BATTERY TRANSFER Transfer Time:2-4 milliseconds Low Voltage Transfer to Battery Power (Setpoint):83 High Voltage Transfer to Battery Power (Setpoint):147 SPECIAL FEATURES Grounding Lug:Back panel grounding lug Cold Start (Startup in Battery Mode During a Power Failure):Cold-start operation supported High Availability UPS Features:Hot swappable batteries Green Energy-Saving Features:Individually controllable load banks Item Dimension (L"xW"xH"): 22.9 x 19.3 x 7.9