| OVERVIEW | |
|---|---|
| PDU Type | Monitored |
| INPUT | |
| PDU Input Voltage | 208 240 |
| Recommended Electrical Service | 60A 208/240V with IEC309 60A Blue (3P+E) outlet |
| Maximum Input Amps | 45 |
| PDU Plug Type | IEC-309 60A BLUE (3P+E) |
| Input Phase | 3-Phase |
| Input Cord Length (ft.) | 6 |
| OUTPUT | |
| Output Capacity Details | 18.7kW (240V), 16.2 (208V) total capacity 26A max per output phase (L1-L2, L2-L3, L3-L1) 20A max per breakered outlet bank 12A max per C13 outlet |
| Frequency Compatibility | 50 / 60 Hz |
| Output Receptacles | (36) C13 |
| Output Nominal Voltage | 208 240 |
| Overload Protection | 6 20A circuit breakers, 1 per outlet bank |
| Front Panel LCD Display | |
| Current Measurement Accuracy (Amps) | +/-1% |
| Voltage Measurement Accuracy (Volts) | +/-1% |
| Power Measurement Accuracy (Watts) | +/-1% |
| PHYSICAL | |
| Form Factors Supported | Vertical rackmount installation supported with included mounting brackets supports toolless mounting in button-mount compatible racks |
| Material of Construction | Metal |
| PDU Form Factor | Vertical (0U) |
| ENVIRONMENTAL | |
| Operating Temperature Range | 32 to 122F (0C to 50C) |
| Storage Temperature Range | -30oC to +60oC (-22oF to +140oF) |
| Relative Humidity | 5 to 95% non-condensing |
| COMMUNICATIONS | |
| SNMP Compatibility | Pre-installed LX platform network interface |
| SPECIAL FEATURES | |
| High Availability PDU Features | Auto Probe Monitoring (included) |
| Certifications | |
| Tested to UL 60950-1 | 2007 R10.14 (USA), CAN/CSA-C22.0 No 60950-1-07-A1:2009 A2:2014 (Canada), Class A Part 15 (EMI), NOM (Mexico), RoHS compliant, TAA Compliant |
| Item Dimension (L"xW"xH") | 10 x 76 x 7 |
| Weight | 39 lbs |
| Warranty Information | 2-year limited warranty |
Reports input current per phase (L1, L2, L3) and output current for each breakered load bank (B1-B6) Outlets are color-coded and labeled for phase and load bank identification L1-L2 feeds black outlets (B1 and B4) L2-L3 feeds dark-gray outlets (B2 and B5) L3-L1 feeds light-gray outlets (B3 and B6)
Touchscreen LCD reports NETWORK DATA (IP address, Subnet Mask, Gateway, MAC Address, Device Name, Model, Serial Number), INPUT PHASE DATA (Amperage, Wattage, Voltage per phase, plus Unbalance percentage), LOAD BANK DATA (Amperage, Wattage, Voltage per load bank, plus total PDU output in watts), CONFIGURATION DATA (Listing of current configuration settings), ENVIRONMENTAL DATA (Reports data and status of E2 sensor modules Sensor options are available for temperature and humidity, plus input and output dry contacts), MOBILE ACCESS (Generates a unique QR code to view reported PDU details on a mobile device)